Shielded cable Cerviflam N2XCH 061 kV CPR

Shielded halogen free power cable for use in industrial processes in fixed installations where certain protection against electromagnetic interferences is required. With 3 conductor configuration, specially suitable for the connection of variable frequency drives and motors.
Suitable for indoor and outdoor installations. The concentric conductor can be used as a neutral,

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Shielded cable Cerviflam N2XCH 0,6/1 kV CPR
~\ImgCli\FOTO2_1192.jpg
Shielded halogen free power cable for use in industrial processes in fixed installations where certain protection against electromagnetic interferences is required. With 3 conductor configuration, specially suitable for the connection of variable frequency drives and motors.
Suitable for indoor and outdoor installations. The concentric conductor can be used as a neutral, protective conductor or earth conductor as long as the regulatory framework allows it. At the same time, it can also be used as a screen. Specially recommended when zero halogen emission in case of fire is required.
Protegido electromagneticas
No propagador de la llama
No propagador incendio
Libre halogenos
Humos baja opacidad
Construction
1. Conductor
Bare copper
· < 25mm2: Class I
· From 25mm2 (inclusive): Class II (Circular or sector shaped, compacted in the larger cross sectional areas)
2. Insulation
XLPE (Cross-linked polethylene)
Identification: HD 308 S2. See attached table.
3. Composition
Insulated conductors laid up together
4. Bedding
Halogen free compound
5. Screen
Copper wires concentric conductor + counter helix copper tape
*The cross-sectional area of the screen is specified in the cable composition, after the cross sectional area of the conductors, separated by: /
6. Outer sheath
Halogen free compound
Colour: Black
Technical characteristics
1. Operating voltage
600/1000 V
2. Test Voltage
4000 V
3. Operating Tª (conductor)
-5°C +70°C
4. Min. bending radius
*See attached table
Standards / Properties
1. Reference standards
VDE 0276-604
2. CPR Classification (Euroclass)
Dca
(According to UNE-EN 50575)
3. Fire Retardant
VDE 0482-266-2-4/IEC 60332-3-24 (Cat.C)
4. Halogen free
IEC 60754
5. Low smoke emission
IEC 61034